OMEGALUX Studio — copper and silver logo
Lighting Journal ↗

How to review DIALux lux levels and uniformity on a UAE project

Lighting engineers reviewing an office lighting calculation and uniformity map

Start with the room reference

Commercial lighting consultants in Dubai can resolve a surprising number of discrepancies by asking which task, working-plane height and operating scene each DIALux row represents.

Consultant comparing a reception counter section with a working-plane overlay on a monitor

A reception desk, a vertical display and the floor beside them need different calculation surfaces because illuminance depends on the direction of the receiving plane.

One reception counter with horizontal writing surface, upright signage and adjacent floor clearly visible

Read the darkest point

Suppose an office task area averages 500 lx with a minimum of 250 lx: its minimum-to-average uniformity is 0.50, so it would miss an illustrative project target of 0.60 despite meeting a 500 lx average.

Office workstations with a shaded perimeter desk and lux meter under the shelf

Before adding fittings, inspect the grid point in section for an overhead bulkhead, tall partition or incorrect luminaire orientation.

Sectional perspective of a tall acoustic screen cutting light off one desktop

Replacing a narrow-beam optic with a wider distribution may lift the minimum between fittings, but rerun the perimeter and glare checks before accepting the change.

Pair of removable narrow and wide beam lenses beside overlapping light pools on desks

Check watts and maintained output separately

For a Masdar City office seeking sustainable lighting solutions, a 600 W installed lighting load across 100 square metres gives an illustrative 6 W/m², with the applicable allowance taken from the approved project brief.

Sun-shaded office floor model with a lighting circuit schedule and input power meter

Compare the proposed system watts and photometric file at the specified drive current, then document the maintenance factor and cleaning interval used for maintained lux.

Labelled photometric sample on a bench beside a driver and a maintenance log with indistinct writing

In the OMEGALUX Lighting Guide, upload the text-based report and compare every Light scene 1 working plane across continuation pages, checking repeated room names against their storey and index.

Architect reviewing a multipage working-plane schedule with storey tabs and highlighted room rows

Lighting Guide · Discuss your project